Detcon 700 Series Remote Sensor/Alarm Relay Module With H Instrukcja Użytkownika

Przeglądaj online lub pobierz Instrukcja Użytkownika dla Sprzęt komputerowy Detcon 700 Series Remote Sensor/Alarm Relay Module With H. Detcon 700 Series Remote Sensor/Alarm Relay Module With HART Interface User Manual Instrukcja obsługi

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj

Podsumowanie treści

Strona 1 - With HART Interface

INSTRUCTION MANUAL Model 700 Series Remote Sensor/Alarm Relay Module With HART Interface DETCON, Inc. 3200 Research Forest Dr., T

Strona 2

700 HART-RAM I.M. The user interface of the HART-RAM is designed to mimic that of the Model 700 Gas Sensor. However, only the functi

Strona 3 - Table of Figures

700 HART-RAM I.M. 3. Set-up and Normal Operation In normal operation, the HART-RAM display continuously shows the current sensor re

Strona 4

700 HART-RAM I.M. 3.2 Set AutoSpan Level Set AutoSpan Level is used to set the span gas concentration level that is being used to c

Strona 5 - 1. Introduction

700 HART-RAM I.M. The three menu items for relay output set-up are Alarm1 Settings, Alarm2 Settings, and Fault Settings. They are u

Strona 6 - Figure 2 HART-RAM Mounting

700 HART-RAM I.M. 3.5 Signal Output Check Signal Output Check provides a simulated 4-20mA output. The simulation allows the user

Strona 7 - 1.3 Field Wiring

700 HART-RAM I.M. ALM1ALM2 FLTNO NC COM NO NC COM NO NC COMJ7J2J1J4INSENSOROUT++mAABmAAB+ABK1K3K2Input Power andmA/HART OutputModbus

Strona 8 - ™ Interface

700 HART-RAM I.M. 6. HART Operator Interface The HART-RAM provides the ability to interface with the sensor via the HART Interface.

Strona 9 - 2. Operator Interface

700 HART-RAM I.M. Primary Variables • Concentration – the value of the gas concentration measured by the sensor. The units of meas

Strona 10 - 700 HART-RAM I.M

700 HART-RAM I.M. Figure 11 Identification HART Tags • Tag – Text that is associated with the field device installation. This text

Strona 11 - 3.1 View Sensor Status

700 HART-RAM I.M. 6.2.1 Device Status Device Status contains one screen that shows the status of the sensor and the HART-RAM. The

Strona 12 - 3.3 Set Serial ID

700 HART-RAM I.M. 700 HART-RAM I.M. ii This page left intentionally blank Shipping Addr

Strona 13

700 HART-RAM I.M. • Clearing Fault – The sensor reading failed to clear after removal of span gas during an AutoSpan sequence • S

Strona 14 - 4. HART Interface

700 HART-RAM I.M. Figure 13 FP Configuration Setup This screen will vary depending on the type of Model 700 sensor attached to the

Strona 15 - Input Power and

700 HART-RAM I.M. TP • Heater Power • Heater Voltage • Sensor Resistance • Heater Current • Sensor Life Note: The values above

Strona 16 - 6. HART Operator Interface

700 HART-RAM I.M. Auto Zero Auto Zero function is used to zero the sensor. Local ambient air can be used to zero most sensors as lo

Strona 17 - 6.1.2 Identification

700 HART-RAM I.M. Auto Span consists of entering “Autospan Cal” and following the display. The procedure will ask for the applicatio

Strona 18 - 6.2 Diagnostics Menu

700 HART-RAM I.M. NOTE 2: If the sensor fails the stability criteria, a “Stability Fault” will be declared and a “Fault Detected” me

Strona 19 - 6.2.2 Sensor Status

700 HART-RAM I.M. Loop Test 1) Ensure that the DVM is connected as prescribed in Figure 15: a) Disconnect the wire from the HART Co

Strona 20 - 6.3 Device Setup Menu

700 HART-RAM I.M. • Date – Gregorian calendar date that is stored in the field device. This can be used by the user in any way. The

Strona 21

700 HART-RAM I.M. 700 HART-RAM I.M. Rev. 0.0 Page 24 of 24 9. Spare Parts Part Number Spare Parts

Strona 22 - 6.3.2 Calibration

700 HART-RAM I.M. 700 HART-RAM I.M. iii Table of Contents 1. Introduction ...

Strona 23 - Auto Span

700 HART-RAM I.M. 700 HART-RAM I.M. iv This page left intentionally blank Shipping A

Strona 24

700 HART-RAM I.M. 1. Introduction 1.1 Description The Model 700 Remote Sensor/Alarm Relay Module with HART Interface (known as t

Strona 25 - D/A Trim

700 HART-RAM I.M. 5.5"5.2"5.825"Ø0.2750 x2MountingBoltWall (or othermounting surface)4.35"Three - 3/4"NPT Fi

Strona 26 - 6.3.3 HART Setup

700 HART-RAM I.M. connectors (Figure 5). To install the electronics package, properly align the plug-in connector and gently push t

Strona 27 - 8. Specifications

700 HART-RAM I.M. The user will typically connect the 700 Gas Sensor directly to the HART-RAM if there is no requirement for remote s

Strona 28 - 10. Revision Log

700 HART-RAM I.M. The recommended cable for remote sensor separation is Belden 1502P (18AWG unshielded pair for power and 22AWG shie